Description:
GXO/I – 1936 – Series termination kits are heat shrinkable type, designed for 3 core extruded dielectric, shielded, armoured/unarmoured XLPE/EPR/PVC Insulated cables upto 36 KV rated voltage (19/33KV, Um=36KV). Our kits has been designed to provide the basic important functions required for medium voltage power cable accessories including the electrical performance, stress relief measures, environmental seal, mechanical fatigues & other related performance parameters laid down in different countries for various service conditions. These are designed, manufactured and tested according to requirements of the local & internationally accepted standards.
Salient Features:
Specifications:
| Test Sequence | Requirement Test Value | Results |
|---|---|---|
| A.C. Voltage Withstand (Dry), 5 Min | No Flashover @85.5KVac | Pass |
| D.C. Voltage Withstand, 15 Min | No Flashover @76KVac | pass |
| A.C. High Voltage (Wet) only for Outdoor terminations, 1min | No Flashover @76 KVac | Pass |
| Partial Discharge | No Flashover @33KVac | < 10 Pc |
| Impulse Withstand Voltage | No Flashover @170KVp | No Flashover |